RT 2000
Flexible split-core Rogowski coil for the electronic measurement
of AC waveform currents, with galvanic separation between the
primary circuit (power) and the secondary circuit (measurement).
The patented Perfect Loop Technology definitely solves the problem
of the Rogowski coil opening by introducing a specific magnetic
device. This dramatically reduces both the error due to the position of
the measured conductor within the sensor, and the error due to the
proximity of external conductors.
Features
● Split core type
d I P
Output voltage (instantaneous) 2) V out = M × V
I PN
M
V out
V out
L S
R S
Electrical data
Primary nominal rms current 2000 A
Mutual inductance transfer ratio 1) (± 5 %) 0.064 μH
d t
Output voltage (sinusoidal wave) 2) V out = 2 × π × M × f × I P AC V
Example: @ 50 Hz, 500 A V out = 2 × π × 64 × 10 -9 × 50 × 2000 = 40.2 mV
Coil inductance (± 5 %) 190 μH
Coil resistance T A = 20 °C typical 60 ?
High cut-off frequency 2) (+ 3 dB) 500 kHz
● ? 125 mm sensing aperture for
non-contact measurement
● 1.5 m output cable
● Insulating plastic case recognized
according to UL 94-V0.
Advantages
● Thin, lightweight and flexible
● Easy installation suitable even for
the most confined spaces
● Very low positioning error.
Accuracy - Dynamic performance data
ε L Linearity error none
TCM Temperature coefficient of M 30 ppm/K
ε P Positioning error 3) max 0.65 %
General data
T A Ambient operating temperature (90 % RH ) - 10 .. + 65 °C
T S Ambient storage temperature - 25 .. + 70 °C
m Mass 90 g
IPxx Protection degree IP 2X
Standards Safety IEC 61010-1: 2001 2nd edition
IEC 61010-2-032: 2002
IEC 61010-031: 2002 + Amd 1: 2008
Applications
● Power meters
Current measurement for active
Power calculation.
● Energy sub-meters
For energy efficiency monitoring,
consumption analysis and costs
allocation.
● Power quality monitoring
● Condition monitoring
(e.g. Motor loads such as
conveyers, pumps or HVAC).
● Distributed measurement
systems.
Notes :
1)
2)
3)
LEM provides uncalibrated coils with up to 5 % manufacturing tolerance.
Calibration must be performed within the final application.
Open circuit condition (no load).
Considering a primary conductor of at least ? 15 mm perpendicular to
Application domain
● Energy Solutions.
the RT loop.
N° 97.F9.69.000.0
Page 1/4
11December2013/version 3
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
www.lem.com
相关PDF资料
RT 500 SENSOR CURRENT 500A MOD
RT1A050ZPTR MOSFET P-CH 12V 5A TSST8
RTF015N03TL MOSFET N-CH 30V 1.5A TUMT3
RTF015P02TL MOSFET P-CH 20V 1.5A TUMT3
RTF020P02TL MOSFET P-CH 20V 2A TUMT3
RTF025N03TL MOSFET N-CH 30V 2.5A TUMT3
RTL030P02TR MOSFET P-CH 20V 3A TUMT6
RTL035N03TR MOSFET N-CH 30V 3.5A TUMT6
相关代理商/技术参数
RT 230/18 制造商:BlockMaster Electronics 功能描述:Bulk
RT 230/22 制造商:Blockmaster Electronics 功能描述:
RT 230/25 制造商:BlockMaster Electronics 功能描述:Bulk
RT 230/45 制造商:BlockMaster Electronics 功能描述:Bulk
RT 2MS 制造商:Cooper Hand Tools / Weller 功能描述:TIP POINTED 0.8MM MIL SPEC 制造商:WELLER 功能描述:TIP, POINTED, 0.8MM, MIL SPEC 制造商:Cooper Hand Tools / Weller 功能描述:TIP, POINTED, 0.8MM, MIL SPEC; Tip / Nozzle Width:0.8mm; Tip / Nozzle Style:Round; For Use With:WMRS Micro Soldering Station; Length:42mm; Tip Size A x B:Round 0.4mm ;RoHS Compliant: NA
RT 30/12 制造商:BlockMaster Electronics 功能描述:Bulk
RT 30/15 制造商:BlockMaster Electronics 功能描述:Bulk
RT 30/18 制造商:Blockmaster Electronics 功能描述: